PGFM Series GFCI Ground Fault Protection Sensing Module

The LineGard™ PGFM GFCI Sensing Module is a ground fault or equipment leakage sensing device designed and manufactured by North Shore Safety, a leader in innovative safety products.

Manufacturer
Airpax
Part No
PGFM
Category
Airpax Circuit Breakers

Our engineering team reviews your quote and sample requests against your project's technical specification and required quantities. We respond within 24 hours at the latest with a formal quotation, delivery schedule and, where applicable, alternative configuration proposals.

Overview

The LineGard™ PGFM GFCI Sensing Module is a ground fault or equipment leakage sensing device designed and manufactured by North Shore Safety, a leader in innovative safety products.

The PGFM operates in tandem with an approved Airpax LEL Series, UL 489 listed circuit breaker, with shunt trip and auxiliary switch. The combined assembly is recognized as a Class A UL 943 rated device. The sensing module is available in models to operate at supply voltages of 120 VAC or 240VAC and can monitor single and split phase circuits.

These devices meet the requirements of OSHA 29 CFR1926.404 (b)(1)(ii) and OSHA 29 CFR 1926.405 (a)(2)(ii)(G).

Features

  • Power and fault status indicators
  • Provides identification of a ground fault vs. short circuit trip
  • Chemical and UV resistant enclosure
  • Trip level of sensing device 5mA ± 1mA Class A UL 943
  • Sensing module operates at 120VAC or 240VAC, single phase
  • Unit operating temperature is -35°C to +66°C
  • Accommodates up to 2 wires, 10 AWG, twisting of the wires is required

Part Numbers

Specifications

TypeE-11 GFP - UL 943 Category FTTJ2 when used in tandem with Airpax LEL series UL 489 listed circuit breaker with shunt trip
Operating Voltage120 VAC or 120/240 VAC
Interrupting VoltageRating of UL 489 listed circuit breaker
Sensing Coil Voltage Limit600 VAC maximum
Phase InterruptSingle (120 VAC 3 wire) and Split (120/240 VAC 4 wire)
Interrupting CurrentRating of UL 489 listed circuit breaker
Trip Time of Combined Assembly100mS or less (60mS nominal)
Trip Level5mA +/- 1mA
Frequency50/60 Hz
Operating Temperature-35°C to +66°C
Reset TypeAutomatic on power up
Note:
1. Manual configuration should be specified if automatic start-up after power restoration of circuit power creates an unsafe condition.
2. As per UL 943 requirements, portable devices may require breaking of neutral during ground fault detection. Please contact the factory.
3. Please contact Airpax for optional ELCI, UL 1053 compliant devices.

Documents & Downloads

Part NumberFile DateFile TypeSizeDownload
PGFM12/07/2023.PDF447KB